VBA216F Ball Valve

  • Vertical installation of horizontal piping or horizontal installation of vertical piping.
  • When mounting the actuator in the fields, before installing the actuator, use an adjustable wrench to manually rotate the valve stem several times. This rotation breaks the torque that may have built up during long-stem storage.
  • Pay attention to medium flow direction, make sure  the valve to move  in the proper direction, wire the input lines to the electric actuator correctly.

Rated rotary angle: 90°(adjustable)
Nominal pressure rating: PN16
Flow characteristic: Equal percentage
Rangeability: See Table. 1
Leakage rate: £0.01% of kVS
Valve body: End connections:                            Flanged( ISO7005-2)

Material:                                        Cast Iron(body)

Dimensions: See Fig.2
Medium: Chilled and hot water, 50% glycol solution
Working temperature: -5 … 110 °C

  • Low seat leakage rate.
  • Accurate positing to ensure state-of-the-are temperat control.
  • Easy mounting of directly coupled with electric actuator